Start Up adding Pyxis probes.

Pyxis Sensor Installation, Start UP

When first installing Pyxis Modbus (digital) Inline probes each probe will need to be programmed with a unique address. This is the slave address. 

This programming is accomplished using ZEUS software. No additional equipment or software is required. 

NOTE you must be using THOR compatible Pyxis Brand Modbus probes. To determine if a Pyxis Probe is THOR compatible please refer to the article found at the following link. 

All THOR compatible probes ship with the same starter address. This is required so that the THOR digital controller will be able to identify the probe during initial installation. As all probes ship with same starter address only ONE new unprogrammed probe may physically attached to the modbus cable. Once the first probe has been programmed with an address of 1-8, THEN and ONLY THEN can the next probe be physically attached to the cable. The first probe may be left on the cable as the address of the first probe has been changed from the default starter address and will not conflict with second probe. This process is repeated until all probes have been programmed. 

If multiple probes all with the factory set starter address are connected to the cable at the same time unexpected results will occur and programming will fail.

Please see the video tutorial on Adding Modbus Probes for detailed instructions for adding and programming Pyxis brand Modbus probes here: https://youtu.be/NPipAuJVelo

For detailed instruction on how to physically connect Pyxis probes to the Modbus cable please refer to the article found at the following link

At some future point if you are adding a new probe (not replacing one) you do not need to remove any of the existing probes. The existing probes have had their address changed to a value of 1 - 8, these addresses will not conflict with the factory set starter address of the new probe. 

See Replacing Modbus Probes for detailed instructions when replacing or taking a probe out of service. 
    • Related Articles

    • Pyxis probes and THOR controller

      THOR Digital Controllers are compatible with Pyxis Modbus Inline Probes that are factory programmed with THOR compatible firmware.   It is important to note that only Pyxis Modbus (Digital) probes with the ERP firmware are compatible with THOR ...
    • Connection order for Pyxis Probes

      Pyxis Modbus/Digital probes are connected to THOR Digital Controllers using a single cable. This factory installed cable provides both power and data communications for all inline probes connected to the cable (bus).  All probes are externally ...
    • Modbus TCP/IP

      THOR comes with MODBUS TCP/IP native to the operating system and ships with Ethernet communications on board. The default status of the onboard MODBUS server is Inactive and must be turned on to operate.  Operator will require a knowledge of MODBUS ...
    • Riess GmbH Free Chlorine Sensor

      Riess brand free chlorine sensor commissioning, installation and general instructions may be found in the attached Operating Instruction manual.
    • ERP712SS Sensor pH and ORP for recreational water

      The ERP712SS is part of the Pyxis brand of pH/ORP digital sensors. Please see attached Specification sheet and User Manual for sensor installation and maintenance information.