How to configure the Scheduled Feed

SCHEDULED FEED, BIOCIDE FEED

The SCHEDULED Feed, sometimes referred to as a BIOCIDE Feed, drives the output (relay) on a scheduled day or days of the week for the user defined duration (expressed in MINUTES). The feed will begin at the defined "Start Time". The SCHEDULED Feed runs on 28 day calendar. The SCHEDULED Feed offers a "Schedule Frequency" option, this option provides the ability to repeat the schedule on weekly intervals (Every week, Every other week, and Every third week).

To configure the Scheduled Feed:
Enable - Slide the Toggle to GREEN, this will enable the output
Description - User provided Name for the output. This will be displayed in the user interface
Start Time -  Time is entered in 24 hour format (hh:mm) for example entering the start time as 09:00 is 9:00 a.m.  Entering the start time as 15:00 is 3:00pm. The Start Time represents the time of day the relay will turn on
Duration - Enter the amount of time for the relay to run. This value is entered in MINUTES
Day(s) of Week - From the drop down menu select the day or days of week that the relay will run. This drop down menu offers multi-select
Schedule Frequency - From the drop down menu select the frequency at which the schedule will repeat. Options are: Every Week, Every other week, Every Third week. 
Digital Lockout - From the drop down select digital outputs that will be locked out (not able to run) while the relay you are configuring is running
Analog Lockouts - From the drop down select analog outputs that will be locked out (not able to run) while the relay you are configuring is running
Additional Lockout After Feed - This option allows you to lockout relays for a defined period AFTER the completion of the scheduled feed. Duration of time is expressed in Minutes
Pre-Blowdown - This option allows for a blowdown PRIOR to the scheduled feed beginning. 
      Blow Down Output - from the drop down select the bleed or blow down output
      Input - from the drop down select the input that is used for the blow down (typically conductivity)
      Setpoint - enter the target setpoint you wish to meet prior to the scheduled feed starting
      Duration - this is the amount of time the pre-blowdown may run in the event the pre-blowdown setpoint is not reached.

    • Related Articles

    • Feed Types

      THOR digital controllers offer a variety of Feed Types meeting many feed application requirements. Below is a list of available feed types. For more details for a specific feed type and related feed options please see the article for that specific ...
    • FLOW Feed

      The FLOW Feed drives an output (relay) for a defined duration of time (minutes) after a specified volume has been reached on a meter input.  A (water) meter input is required to operate the Flow feed. The FLOW feed measures volume passing through a ...
    • PERIOD FEED

      The PERIOD FEED is used to drive an output using a PERIOD (cycle time) and percentage of the defined PERIOD called Feed on Percentage. The PERIOD FEED is time based and does not rely on a sensor input.  To configure the PERIOD FEED complete the ...
    • Changing Feed Type

      All output feed types (i.e. Cycle Feed) may be edited at any time. The EDIT option is found in the drop down menu under the ACTIONS header on the summary page. Click on the three action dots under the Actions header this will display the drop down ...
    • Minimum Relay Run Time

      When a relay is turned on or off the relay has a default STATE time of 5 seconds. This 5 second minimum STATE time is built into the operation system and may not be overridden by a user.  Motorized valves often require a minimum amount of time to ...