Feed types, Feed options

Feed Types

THOR digital controllers offer a variety of Feed Types meeting many feed application requirements.
Below is a list of available feed types. For more details for a specific feed type and related feed options please see the article for that specific feed type.

DIGITAL FEEDS - Powered relay
1. Value Feed - sometimes referred to as a setpoint.
2. Period Feed - sometime referred to as Time & Percent
3. Scheduled Feed - sometimes referred to as Biocide Feed
4. Cycles Feed - using two conductivity inputs to  adjust cycles based on dynamic make up water conductivity values
5. Linked Feed - sometimes referred to as feed after or feed and bleed
6. Flow Feed - feed based on amount of gallons from a connected meter
7. Time Proportional 
8. Intermittent Sample Feed - typically used in boiler applications. Provides for sample and cooling time
9. Bleed by Volume - requires two connected meters
10.  Alarm Relay - triggers relay when an alarm condition exists on the controller. Typically used to drive a local visual and/or audible alarm.

Options vary by feed type, certain feeds offer one or more of the following options the user may select when configuring the feed type.
a) slug feed - manual mode or manual feed
b) lockouts
c) lock out after feed, or additional lockout
d) pre-bleed, or bleed and feed
e) output modulation (period and percent) 
f) spike feed

MODBUS TCP IP
Thor comes with MODBUS TCP/IP standard. The user will need to set the subnet in the LAN settings and connect to the local Network using the included Ethernet port inside of the digital controller. This is an RJ45 connection. See the article titled MODBUS TCP/IP for more information and the MODBUS programming supplement. 

With the purchase of an optional Analog Module the following feeds are also available:
Analog output
1. Proportional output control - requires a compatible pump
2. PID control - operator required to have working knowledge of PID control
3. Retransmit - transmitting 4-20mA current to a third party system






    • Related Articles

    • Digital and Analog Outputs (Relays)

      THOR Digital Controllers offer two output (relay) types, Digital and Analog.  Digital Outputs come standard with THOR Controllers: THOR L800 has 8 Digital powered relays  THOR L400 has 4 Digital powered relays Digital relays are powered and offer ...
    • Modbus TCP/IP

      THOR comes with MODBUS TCP/IP native to the operating system and ships with Ethernet communications on board. The default status of the onboard MODBUS server is Inactive and must be turned on to operate.  Operator will require a knowledge of MODBUS ...
    • Changing Feed Type

      All output feed types (i.e. Cycle Feed) may be edited at any time. The EDIT option is found in the drop down menu under the ACTIONS header on the summary page. Click on the three action dots under the Actions header this will display the drop down ...
    • Value Feed, Setpoint Feed

      The Value Feed, sometimes referred to as a Setpoint Feed, drives the output by the value provided by a target input (i.e. a probe) to determine when an output (relay) turns on or off.  Configuration options Enable - Slide the Toggle to GREEN, this ...
    • FLOW Feed

      The FLOW Feed drives an output (relay) for a defined duration of time (minutes) after a specified volume has been reached on a meter input.  A (water) meter input is required to operate the Flow feed. The FLOW feed measures volume passing through a ...