The FLOW Feed drives an output (relay) for a defined duration of time (minutes) after a specified volume has been reached on a meter input. A (water) meter input is required to operate the Flow feed.
The FLOW feed measures volume passing through a meter. When the meter reports the target volume has been reached, the Output (relay) will run for the defined "Duration in Minutes". This process repeats each time the target volume is reported by the meter.
Enable -
Slide the Toggle to GREEN, this will enable the output
Description -
User provided Name for the output. This will be displayed on the user
interface
Input -
From the drop down menu select the meter that the relay will read to
drive relay actions
Volume Increment - Enter the volume (typically expressed as Gallons or Liters) that must pass through meter to activate the output
Duration in Minutes - Enter the amount of time (in minutes) the output will run after meeting the Volume Increment
Digital
Lockout - From the drop down select digital outputs that
will be locked out (not able to run) while the relay you are
configuring is running
Analog
Lockouts - From the drop down select analog outputs
that will be locked out (not able to run) while the relay you are configuring is running
Limits -
The Limits option will shut down an output once it has exceeded the
permitted run time of the selected FREQUENCY (Hourly or
Daily) the LIMIT is expressed as MINUTES. If a
LIMIT is configured as
Frequency = DAILY and TIME = 250:
In
the event the relay runs for 250 minutes between Midnight to Midnight
the relay will be shut down for the balance of the current DAY. At
midnight the timer will reset and the relay will be able to
run up to 250 minutes for the then current day.
High
& Low Alarm - These optional alarms measure time. Alarms
may be configured for Active (running too long) or Inactive (running
for less than expected)